Acti9 xC60 3P C 6A MCB IS/IEC 60898-1 - Schneider
Schneider Electric A9N3P06CGN - Acti9 xC60 3P C 6A MCB
The Schneider Electric Acti9 xC60 A9N3P06CGN is a 3-pole miniature circuit breaker (MCB) designed for protection against overload and short-circuit currents in low-voltage AC distribution systems. It features a 6 A rated current, C tripping curve, and 10 kA breaking capacity in compliance with IS/IEC 60898-1. The breaker is suitable for isolation, DIN rail mounting, and integration with auxiliary and Vigi accessories for advanced monitoring and protection functions.
| Manufacturer | Schneider Electric |
|---|---|
| Product Reference | A9N3P06CGN |
| Product Range | Acti9 |
| Product Series | xC60 |
| Product Name | XC60 |
| Product Type | Miniature Circuit Breaker (MCB) |
| Device Short Name | xC60 |
| Application | Distribution |
| Poles Description | 3P |
| Number of Protected Poles | 3 |
| Rated Current (In) | 6 A |
| Network Type | AC |
| Trip Unit Technology | Thermal-Magnetic |
| Tripping Curve | C Curve |
| Network Frequency | 50/60 Hz |
| Rated Operational Voltage (Ue) | 220-240 VAC, 380-415 VAC |
| Magnetic Tripping Limit | 5 to 10 × In |
| Rated Breaking Capacity (Icn) @ 240 VAC | 10 kA |
| Rated Breaking Capacity (Icn) @ 415 VAC | 10 kA |
| Breaking Capacity Standard | IS/IEC 60898-1 |
| Current Limitation Class | Class 3 |
| Rated Insulation Voltage (Ui) | 500 VAC |
| Suitable for Isolation | Yes |
| Contact Position Indicator | Yes |
| Positive Contact Indication | Yes |
| Local Signalling | ON/OFF Indication |
| Control Type | Toggle |
| Mounting Mode | Clip-On |
| Mounting Support | 35 mm DIN Rail |
| Comb Busbar Compatibility | Top: Yes |
| Number of 9 mm Modules | 6 |
| Height | 85 mm |
| Width | 54 mm |
| Depth | 77.5 mm |
| Net Weight | 0.31 kg |
| Colour | White (RAL 9003) |
| Mechanical Durability | 20,000 Cycles |
| Electrical Durability | 20,000 Cycles |
| Terminal Type | Tunnel Type |
| Flexible Cable Capacity | 16 mm² |
| Rigid Cable Capacity | 25 mm² |
| Connection Technology | BiConnect |
| Connection Position | Bottom |
| Wire Stripping Length | 13 mm |
| Tightening Torque | 2 N·m |
| Earth Leakage Protection | Separate Vigi Add-on Block |
| Compatible Accessories | C60 Accessories, C60 Auxiliary Devices |
| Overvoltage Category | IV |
| Degree of Protection | IP20 |
| Degree of Protection in Enclosure | IP40 |
| Pollution Degree | 3 |
| Tropicalisation | Level 2 (IEC 60068-1) |
| Relative Humidity | 95% at 55°C |
| Operating Temperature | -30°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Standard Compliance | IS/IEC 60898-1 |
| Warranty | 18 Months |
| Lifecycle Carbon Footprint | 9 kg CO₂ equivalent |
| Recyclability Potential | 1% |
| Characteristic | Value |
| Protection Type | Overload and Short-Circuit Protection |
| Rated Current | 6 A |
| Tripping Characteristic | C Curve |
| Instantaneous Magnetic Trip | 5 to 10 × In |
| Short-Circuit Breaking Capacity | 10 kA |
| Isolation Function | Yes |
| Contact Status Indication | Positive Contact Indicator |
| Current Limitation | Class 3 |
| Terminal Design | Tunnel Type / BiConnect |
| Flexible Conductors | Up to 16 mm² |
| Rigid Conductors | Up to 25 mm² |
| Busbar Connection | Top Connection |
| Wire Strip Length | 13 mm |
| Installation Method | DIN Rail Mounting |
| Module Width | 6 × 9 mm |
| Mechanical Life | 20,000 Operations |
| Electrical Life | 20,000 Operations |
| Operating Temperature Range | -30°C to +70°C |
| Storage Temperature Range | -40°C to +85°C |
| Humidity Resistance | 95% RH at 55°C |
| Tropicalisation Rating | Level 2 |
| Protection Class | IP20, IP40 in enclosure |
| 3-Pole Protection | Suitable for three-phase distribution circuits |
| C-Curve Characteristic | Ideal for general-purpose and moderately inductive loads |
| High Breaking Capacity | 10 kA short-circuit interruption capability |
| BiConnect Terminals | Improved cabling flexibility and secure connection |
| Isolation Capability | Safe maintenance and downstream isolation |
| Accessory Expandability | Supports auxiliaries, remote monitoring, and Vigi blocks |
| Long Service Life | 20,000 mechanical and electrical operating cycles |