TeSys M-CB THO/MAG 1.6-2.5A ROCKER Schneider
Schneider Electric GV2ME07 TeSys M-CB THO/MAG 1.6-2.5A ROCKER
The Schneider Electric GV2ME07 is a TeSys GV2 thermal-magnetic motor circuit breaker (MPCB) designed for manual motor starting, switching, isolation, and motor protection against overload and short-circuit conditions. It features an adjustable thermal protection range of 1.6 to 2.5 A, a 3-pole design, push-button (rocker) operation, and screw clamp terminals, making it suitable for industrial motor control applications.
| Manufacturer | Schneider Electric |
|---|---|
| Product Series | TeSys Deca |
| Product Name | TeSys GV2 |
| Model Number | GV2ME07 |
| Product Type | Motor Circuit Breaker (MPCB) |
| Device Short Name | GV2ME |
| Application | Motor protection, motor starting, isolation |
| Trip Unit Technology | Thermal-Magnetic |
| Thermal Protection Adjustment Range | 1.6 to 2.5 A |
| Number of Poles | 3P |
| Network Type | AC |
| Network Frequency | 50/60 Hz |
| Utilization Category | Category A (IEC 60947-2), AC-3, AC-3e |
| Control Method | Push Button / Rocker |
| Rated Operational Voltage (Ue) | Up to 690 V AC |
| Rated Insulation Voltage (Ui) | 690 V AC |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Motor Rating @ 400/415 V AC | 0.75 kW |
| Motor Rating @ 500 V AC | 1.1 kW |
| Motor Rating @ 690 V AC | 1.5 kW |
| Magnetic Trip Setting | Approximately 33.5 A |
| Thermal Overload Class | Class 10 |
| Breaking Capacity (Icu) @ 230/240 V AC | 100 kA |
| Breaking Capacity (Icu) @ 400/415 V AC | 100 kA |
| Breaking Capacity (Icu) @ 440 V AC | 100 kA |
| Breaking Capacity (Icu) @ 500 V AC | 100 kA |
| Breaking Capacity (Icu) @ 690 V AC | 3 kA |
| Service Breaking Capacity (Ics) | 100% of Icu up to 500 V AC |
| Rated Continuous Current | 2.5 A maximum setting |
| Mounting Type | DIN Rail or Panel Mount |
| Terminal Type | Screw Clamp Terminals |
| Connection Capacity (Flexible Cable) | Up to 6 mm² |
| Connection Capacity (Solid Cable) | Up to 10 mm² |
| Mechanical Durability | 100,000 operations |
| Electrical Durability | 100,000 operations (AC-3 duty) |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Weight | Approximately 0.26 kg |
| Enclosure Protection | IP20 |
| Impact Protection | IK04 |
| Operating Temperature Range | -20°C to +60°C |
| Storage Temperature Range | -40°C to +80°C |
| Phase Failure Sensitivity | Yes |
| Isolation Function | Suitable for isolation |
| Reset Mode | Manual |
| Actuator Color | Black START, Red STOP |
| Mounting Position | Any position |
| Pollution Degree | 3 |
| Overvoltage Category | III |
| Standards | IEC 60947-1, IEC 60947-2, IEC 60947-4-1 |
| Certifications | UL, CSA, CE, CCC, EAC, ATEX, Marine, CB Scheme |
| RoHS Compliance | Yes |
| Recyclability Rate | 49% |
| Carbon Footprint | 11 kg CO₂ eq. |
| Protection Type | Value |
| Thermal Overload Protection | Adjustable 1.6 to 2.5 A |
| Short Circuit Protection | Thermal-Magnetic Trip |
| Instantaneous Magnetic Trip | Approx. 13 × In (≈33.5 A) |
| Phase Loss Protection | Integrated |
| Motor Starting Protection | Class 10 |