TeSys M-CB THO/MAG 2.5-4A ROCKER - Schneider
The Schneider Electric GV2ME08 is a TeSys GV2 thermal-magnetic motor circuit breaker (MPCB) designed for manual motor control, isolation, overload protection, and short-circuit protection of three-phase motors. It features an adjustable thermal protection range of 2.5 to 4 A, a 3-pole configuration, and push-button (rocker) operation. The device combines motor starter, disconnect switch, and motor protection functions in a compact unit suitable for industrial motor control applications.
| Manufacturer | Schneider Electric |
|---|---|
| Product Series | TeSys Deca |
| Product Name | TeSys GV2 |
| Model Number | GV2ME08 |
| Product Type | Motor Circuit Breaker (MPCB) |
| Device Short Name | GV2ME |
| Device Application | Motor Protection |
| Trip Technology | Thermal-Magnetic |
| Number of Poles | 3P |
| Control Type | Push-button / Rocker |
| Rated Current (In) | 4 A |
| Thermal Protection Adjustment Range | 2.5 to 4 A |
| Magnetic Tripping Current | 74 A |
| Conventional Thermal Current (Ith) | 4 A |
| Rated Operational Voltage (Ue) | 690 V AC, 50/60 Hz |
| Rated Insulation Voltage (Ui) | 690 V AC |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Network Type | AC |
| Network Frequency | 50/60 Hz |
| Utilization Category | Category A, AC-3, AC-3e |
| Phase Failure Sensitivity | Yes |
| Suitable for Isolation | Yes |
| Rated Duty | Uninterrupted Duty |
| Power Dissipation per Pole | 2.5 W |
| Mechanical Durability | 100,000 cycles |
| Electrical Durability | 100,000 cycles (AC-3 / AC-3e) |
| Protection Degree | IP20 |
| Mounting Type | DIN Rail or Panel Mount |
| Mounting Position | Horizontal or Vertical |
| Fixing Method | 35 mm Symmetrical DIN Rail, Screwed Panel Mount |
| Terminal Type | Screw Clamp Terminals |
| Tightening Torque | 1.7 N·m |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Net Weight | 0.26 kg |
| Colour | Dark Grey |
| Pollution Degree | 3 |
| Overvoltage Category | III |
| Operating Temperature Range | -20°C to +60°C |
| Storage Temperature Range | -40°C to +80°C |
| Recyclability Rate | 49% |
| Carbon Footprint | 11 kg CO₂ eq. |
| Compliance | RoHS, REACH |
| Supply Voltage | Motor Power |
| 400/415 V AC | 1.1 kW to 1.5 kW |
| 500 V AC | 1.5 kW to 2.2 kW |
| 690 V AC | 2.2 kW to 3.0 kW |
| Icu @ 230/240 V AC | 100 kA |
| Icu @ 400/415 V AC | 100 kA |
| Icu @ 440 V AC | 100 kA |
| Icu @ 500 V AC | 100 kA |
| Icu @ 690 V AC | 3 kA |
| Ics @ 230/240 V AC | 100% Icu |
| Ics @ 400/415 V AC | 100% Icu |
| Ics @ 440 V AC | 100% Icu |
| Ics @ 500 V AC | 100% Icu |
| Ics @ 690 V AC | 75% Icu |
| Conductor Type | Capacity |
| Solid Conductors | 2 × 1...6 mm² |
| Flexible Conductors (without ferrule) | 2 × 1.5...6 mm² |
| Flexible Conductors (with ferrule) | 2 × 1...4 mm² |
| Category | Details |
| Standards | EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1 |
| Additional Standards | IEC/EN 60335-1 Clause 30.2, IEC/EN 60335-2-40 Annex JJ |
| Certifications | CCC, UL, CSA, EAC, ATEX, Marine |
| Environmental Compliance | RoHS, REACH |